Earthing


Earthing in Electrical Installations: Design, Standards, and Best Practices

Earthing, also known as grounding, is a critical safety measure in electrical installations. It protects human life and electrical equipment by providing a low-resistance path for fault currents to safely dissipate into the earth. This prevents electric shock, fire hazards, and equipment damage.

🛡️ Purpose and Function of Earthing

  • Safety: Prevents electric shock by directing fault current away from users.
  • Equipment Protection: Shields electrical devices from damage due to voltage surges or leakage.
  • System Stability: Helps maintain voltage levels and ensures proper operation of protective devices.

🔗 Components of an Earthing System

  • Earth Electrode: Typically a metal rod, pipe, plate, or strip buried in the ground.
  • Earth Continuity Conductor: Copper or galvanized iron wire connecting the equipment to the electrode.
  • Earthing Pit: Enclosure housing the electrode and conductor, allowing access for testing and maintenance.

📏 General Guidelines for Installation

  • Earth electrodes should be buried vertically at a minimum depth of 3 meters.
  • Earth continuity conductors must be laid straight, not coiled, and securely clamped to the electrode.
  • Minimum conductor size: 4 sq.mm for copper or galvanized iron.
  • All metallic parts of the electrical system, including distribution boards and equipment frames, must be bonded to the earthing system.
  • Periodic testing of earth resistance is essential; values must remain within prescribed limits.

📊 Recommended Earth Resistance Values (NBC)

  • Residential areas: Should not exceed 5 ohms
  • Industrial areas: Should not exceed 1 ohm
  • High voltage installations: Should not exceed 0.5 ohms
  • Hospitals: Should not exceed 1 ohm
  • Telecommunication installations: Should not exceed 10 ohms

🧱 Types of Earthing Systems

Commonly Used Methods

  • Plate Earthing: A copper or galvanized iron plate buried vertically; ideal for low-conductivity soil.
  • Pipe Earthing: A galvanized iron pipe buried vertically; suitable for high-conductivity soil.
  • Strip Earthing: A horizontal copper or GI strip buried in shallow or rocky soil.
  • Rod Earthing: A copper or GI rod driven vertically into the ground; often used in telecom and high-voltage systems.

📘 Indian Standard: IS 3043:2018

The Bureau of Indian Standards (BIS) outlines the national code for earthing systems under IS 3043:2018. Key provisions include:

  • Design Criteria: Number and spacing of electrodes based on load and soil conditions.
  • Material Selection: Approved materials for electrodes and conductors.
  • Installation Practices: Guidelines for placement, connection, and protection of components.
  • Testing & Maintenance: Procedures for periodic resistance testing and system upkeep.

🛠️ Designing an Earthing System

Key Steps

  • Select Earthing Type: Based on soil conditions and installation type.
  • Determine Electrode Quantity and Spacing: Ensure resistance values meet standards.
  • Choose Conductor Type and Size: Based on load and distance to electrode.
  • Design Earthing Pit: Size and structure depend on electrode type and soil.
  • Identify Location: Must be accessible and safe for testing and maintenance.
  • Prepare Detailed Plan: Include layout, material specs, and installation/testing procedures.

🏗️ Installation of Earthing System

Step-by-Step Process

  • Site Preparation: Clear obstacles and mark installation area.
  • Excavation: Dig to required depth and dimensions.
  • Electrode Installation: Secure electrode in place and surround with backfill material.
  • Conductor Installation: Connect conductor to electrode and equipment.
  • Earthing Pit Construction: Build enclosure for access and protection.
  • Testing: Measure resistance and verify system integrity.

🧰 Materials Required (IS 3043:2018)

  • Earth electrode (plate, pipe, rod)
  • Earthing conductor (copper or GI wire/strip)
  • Backfill material (charcoal, salt, soil)
  • Earthing pit (brickwork or concrete)
  • Fasteners and fittings (clamps, bolts)
  • Testing equipment (earth resistance meter)

🧪 Plate Earthing Procedure

As per IS 3043:2018

  • Site Survey and Preparation
  • Plate Selection: Copper or GI plate of standard dimensions
  • Plate Installation: Buried vertically at 3 m depth
  • Conductor Connection: Securely clamped to the plate
  • Pit Construction: Accessible enclosure with inspection cover
  • Testing and Commissioning: Verify resistance values
  • Maintenance: Periodic inspection and testing

🔧 Maintenance of Earthing Systems

  • Visual Inspection: Check for corrosion, damage, or loose connections.
  • Ground Resistance Measurement: Ensure values are within limits.
  • Soil Resistivity Testing: Monitor changes in soil conditions.
  • Pit Maintenance: Keep pit clean and accessible.
  • Conductor Protection: Shield from mechanical damage and corrosion.
  • Record Keeping: Maintain logs of inspections and test results.

🧠 What Matters Most

  • Earthing protects people and equipment from electrical faults.
  • Use copper or GI electrodes and conductors, buried at least 3 meters deep.
  • Follow IS 3043:2018 and NBC guidelines for design, installation, and testing.
  • Maintain resistance values: 5 ohms (residential), 1 ohm (industrial), 0.5 ohms (high voltage).
  • Regular testing and maintenance are essential for long-term safety.
 

Material Used in Plate Earthing as Per CPWD:

1.Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement andwatering pipe of 2.7 metre long etc. with charcoal/ coke and salt.

a. 600 mm X 600 mm X 6 mm thick G.I. plate - 1 No.
b. 20 mm dia. G.I. pipe (medium class) - 2.84 mtr (2.7 + 0.14 mtr@wastage 5% )
c. CI/MS cover plate hinged to frame with Locking arrangement - 1 No.
d. Funnel - 1 No.
e. G.I. nuts and through bolts with washer - 1 No.
f. Charcoal - 96 Kg.
g. Salt - 5 Kg.
h. Common burnt clay F.P.S. (non modular) each bricks class designation 7.5 - 50 Nos.
i.  Cement - 10 Kg.
j.  Fine sand - 30 Kg.
k. With Labour

2. Earthing  with  Copper  earth  plate  600  mm  X  600  mm  X  3  mm  thick  including accessories,  and providing  masonry  enclosure  with  cover  plate  having  locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
 
a. 600 mm X 600 mm X 3 mm thick Copper plate (10.5 Kg)- 1 No.
b. 20 mm dia. G.I. pipe (medium class) - 2.84 mtr (2.7 + 0.14 mtr@wastage 5% )
c. CI/MS cover plate hinged to frame with Locking arrangement - 1 No.
d. Funnel - 1 No.
e. G.I. nuts and through bolts with washer - 1 No.
f. Charcoal - 96 Kg.
g. Salt - 5 Kg.
h. Common burnt clay F.P.S. (non modular) each bricks class designation 7.5 - 50 Nos.
i.  Cement - 10 Kg.
j.  Fine sand - 30 Kg.
k. With Labour

Pipe Earthing as Per IS 3043:2018

Pipe earthing is a type of earthing system that is commonly used in electrical installations. It involves the use of a metal pipe that is buried in the ground to provide a low impedance path to earth. The following is a detailed process for pipe earthing as per IS 3043:2018:

 

Material Used in Pipe Earthing as Per CPWD:

1.Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing  masonry  enclosure  with  cover  plate  having locking  arrangement and watering pipe etc with charcoal/ coke and salt.
 
a. 40 mm dia. G.I. pipe (medium class) - 4.73 mtr (4.5 + 0.23mtr@wastage 5% )
b. CI/MS cover plate hinged to frame with Locking arrangement - 1 No.
c. 40 mm to 20 mm reducer - 1 No.
d. Funnel - 1 No.
e. G.I. nuts and through bolts with washer - 1 No.
f. Charcoal - 64 Kg.
g. Salt - 5 Kg.
h. Common burnt clay F.P.S. (non modular) each bricks class designation 7.5 - 50 Nos.
i.  Cement - 10 Kg.
j.  Fine sand - 30 Kg.
k. With Labour

Maintenance Free Earthing

IS 3043:2018 does not specify any standard for "maintenance-free earthing". However, there are some alternatives to traditional earthing systems that are advertised as "maintenance-free" or "maintenance-friendly".

One such system is the Chemical Earthing System, which uses a chemical compound as an electrode to provide a low impedance path to earth. The chemical compound is placed around a copper electrode, which is then inserted into the ground. The chemical compound enhances the conductivity of the soil, which reduces the earth resistance and improves the performance of the earthing system. Chemical earthing systems are claimed to be maintenance-free and have a longer lifespan compared to traditional earthing systems.

Another alternative is the Copper Clad Steel (CCS) Earthing System, which uses a copper layer over a steel core to provide a low impedance path to earth. The steel core provides strength and durability, while the copper layer provides the conductivity. CCS earthing systems are claimed to be maintenance-free and have a longer lifespan compared to traditional earthing systems.

It is important to note that the effectiveness of any earthing system, including "maintenance-free" systems, depends on the soil resistivity, installation practices, and other factors. It is recommended to consult with a qualified electrical engineer or contractor to determine the most suitable earthing system for a specific application. Additionally, regular inspections and maintenance should be performed to ensure that the earthing system is in good working condition.

Chemical Earthing System

The Chemical Earthing System is not specifically mentioned under any particular code in India. However, it is generally accepted as a viable alternative to traditional earthing systems and is commonly used in many electrical installations.

The Chemical Earthing System typically consists of a copper electrode surrounded by a chemical compound that enhances the conductivity of the soil and provides a low impedance path to earth. The chemical compound may include a mixture of bentonite clay, salt, and other additives.

While there is no specific code for Chemical Earthing Systems, it is important to ensure that the system is installed in accordance with applicable standards and guidelines for earthing systems, such as IS 3043:2018 "Code of Practice for Earthing" and IEEE 80 "Guide for Safety in AC Substation Grounding". Additionally, regular inspections and maintenance should be performed to ensure that the earthing system is in good working condition.

Installation of Chemical Earthing System

The installation process for a Chemical Earthing System generally involves the following steps:

  1. Site Preparation: Identify a suitable location for the earthing system, away from any underground utilities or obstructions. Dig a pit in the soil to accommodate the earthing electrode.

  2. Electrode Placement: Insert the copper electrode into the pit and ensure that it is vertical and centered in the pit. The electrode should be long enough to reach a depth where the soil resistivity is low.

  3. Backfilling: Fill the pit with the chemical compound, which is typically a mixture of bentonite clay, salt, and other additives. The chemical compound should be compacted around the electrode to ensure good contact with the soil.

  4. Connection: Connect the copper electrode to the equipment to be grounded, using suitable copper wires and clamps.

  5. Testing: Perform an earth resistance test to ensure that the earthing system is functioning properly. The test should be conducted in accordance with applicable standards, such as IS 3043:2018 and IEEE 80.

It is important to follow the manufacturer's instructions and applicable standards when installing a Chemical Earthing System. Additionally, regular inspections and maintenance should be performed to ensure that the earthing system is in good working condition.