AC Size Calculator
AC Size Calculator
Find the cooling load and recommended air conditioner tonnage for a room, adjusted for room type, sun exposure, climate and occupancy, plus an estimated running cost.
Room Details
Occupancy load is added for occupants beyond the first 2, who are assumed to be included in the base figure.
Efficiency & Running Cost (Optional)
Power input is estimated as Tonnage × the kW-per-TR figure for the selected star rating. Leave the price blank to skip the running cost estimate.
- This is a quick-sizing estimate for a typical residential or office room. For a hall, an unusually high ceiling, a glass facade, or a commercial space, get a proper heat-load (cooling load) calculation done by an HVAC engineer.
- 1 Ton of Refrigeration (TR) = 12,000 BTU/hr = 3.517 kW of cooling capacity.
- Oversizing an AC causes short-cycling (frequent on/off) and poor humidity removal; undersizing means it runs continuously without reaching the set temperature. Always round up to the nearest standard size rather than down.
Reference Guide: Cooling Load Estimation
1. Base Cooling Load
269 BTU/hr per sq.m (about 25 BTU/hr per sq.ft) is a commonly used rule-of-thumb base rate for a reasonably well-insulated room with a standard 2.7 m (9 ft) ceiling; the height term scales this up or down for a taller or shorter room.
2. Adjustment Factors
Total Load = Adjusted Load + [(Occupants − 2) × 600 BTU/hr] + (Equipment Watts × 3.412)
Each additional person beyond the first two adds roughly 600 BTU/hr of body heat and moisture load. Electronics, kitchen equipment and other heat sources are converted from watts to BTU/hr at 3.412 BTU/hr per watt.
3. Tonnage and Standard Sizes
The calculated tonnage is rounded up to the nearest size commonly sold in India: 0.8, 1.0, 1.5, 2.0, 2.5, 3.0, 4.0 or 5.0 TR.
4. Typical Room Size to Tonnage (Quick Reference)
| Room Area | Typical AC Size |
|---|---|
| Up to 10 sq.m (110 sq.ft) | 0.8 TR |
| 10 – 14 sq.m (110 – 150 sq.ft) | 1.0 TR |
| 14 – 23 sq.m (150 – 250 sq.ft) | 1.5 TR |
| 23 – 37 sq.m (250 – 400 sq.ft) | 2.0 TR |
| 37 – 56 sq.m (400 – 600 sq.ft) | 3.0 TR |
5. Power Input and Running Cost
A 3-star split AC typically draws about 1.4–1.5 kW of electrical input per TR of cooling, a 4-star unit about 1.2–1.3 kW/TR, and a 5-star (or inverter) unit about 1.0–1.1 kW/TR, though exact figures vary by model; check the BEE label on the specific unit you are considering.
Running Cost per Hour = Power Input (kW) × Electricity Price per kWh
K K Kranti
Shares practical MEP calculators, checklists and design guides on MEP Analysis.